    Legrand UPS 1f/1f KEOR S 6000VA, on-line, 6000VA / 5400W, 17 minut, RS232, Tower, krytie IP31

    Vypredané

     
    Produkt je vyradený !

    V našej ponuke nájdete podobné modely. S výberom pomôžeme.

    Kód tovaru

    265248

    PN kód

    310128

    Výrobca
    Záruka

    24 mesiacov

    Alternatívy v kategórií Záložné zdroje UPS

    Popis produktu

    Legrand UPS 1f/1f KEOR S 6000VA

    General features
    - 3kVA to 10KVA Capacity Range
    - 1 Phase Input / 1 Phase Output
    - IGBT Inverter
    - IGBT Rectifier
    - High Efficiency
    - Digital Signal Processor (DSP)
    - High Input Power Factor (PFC)
    - High Output Power Factor
    - Low Input and Output Total Harmonic Distortion (THD)
    - Generator Compatible Operation
    - Standard IP31 Protection for Industrial Applications
    - On Site Modular Paralleling Capability up to 4 Units (except 3kVA)
    - Additional External Chargers for Long Back-Up Time Solutions (6-10kVA only)
    - Availability of Different Communication Types

    Function
    - User friendly diagnostic
    - Advanced management and communication
    - Integrated By-pass for maintenace
    - LCD display with interactive menu

    .

    Keor S 6000 (310128 – 310129)

    Legrand UPS model Keor S 6000 is an uninterruptible power source with IGBT switching technology, high frequency PWM technology, Double Conversion On-line, with the possibility to have N+X on site modular redundancy up to total 4 units, Rated Power 6 kVA – 5.4 kW.

    The architecture of this UPS means it can be installed in a Tower configuration. Two different models are available as internal configuration; internal battery or input isolation transformer. Addition to these configurations, simultaneous using of both internal and external battery is possible by DC switch protections.
    Batteries are lead acid, sealed, free maintenance, valve regulated, and arranged, inside the UPS or external battery cabinet. Internal battery configuration is sized to guarantee a minimum uptime of 20 minutes and at 80% of 0,9PF load.

    The rectifier of the UPS is comprised of a control and regulating circuit (PFC), which, in addition to normal rectifier functions also:
    • Automatically corrects the power factor of the load to restore it to a value of >0.99 with a load applied at the output at 75% of the rated load;
    • Supply the inverter without requiring energy from the batteries, even when the mains voltage is very low;
    • Ensures low total harmonic distortion of the input current without the addition of filters or supplementary parts.

    The bypass circuit is designed and built in compliance with the following:
    - Electromechanical switch
    - Command and control logic managed by a microprocessor that:
    • Automatically transfers the load directly onto the primary mains line without interrupting the power supply if any conditions of overload, over temperature, continuous voltage outside of the tolerances and inverter anomaly arise;
    • Automatically re-transfers the primary mains line load to an inverter line, without interrupting the power supply, once normal conditions of the load have been restored;
    • If the primary mains line and the inverter are not synchronised, the bypass must be disabled.

    The inverter of the UPS is comprised of IGBT technology which provides:
    • Ensures low total harmonic distortion at the output voltage and 0,9 power factor;
    • Provides high efficiency with transformerless design;
    • Supply the load with regulated voltage and frequency.

    A dedicated software of remote monitoring and management, installed on a PC connected to the UPS, allows to check and set all working parameters of Keor S and furthermore, to schedule and program computer remote shutdown. Optional software or Net Interface card (SNMP) allows the multi server shutdown and UPS remote control on the LAN. Also, standard interface board comes with;
    • RS232 Serial Communication Port
    • Emergency Power Off (UPS OFF)
    • Generator Contact (GEN ON)
    • Smart Slot (for optional SNMP)

    Keor S is managed by a microprocessor and is able to display, on a control panel and LCD screen, the alarms and operating modes described below:
    • Line Mode,
    • Backup Mode,
    • ECO Mode,
    • Bypass Supply,
    • Battery Low,
    • Battery Bad/Disconnect,
    • Overload,
    • Transferring with interruption
    • UPS Fault normal operation

    It is possible to change output voltage by 220V, 230V, 240V and frequency by 50Hz or 60Hz from front control panel of Keor S 6kVA. Addition to this, Keor S can be used as 50Hz to 60Hz (or vice versa) Frequency Converter with or without batteries as standard.

    Input, Output and Battery connections are hardwired and protected by suitable MCBs.
    Keor S 6kVA has internal both static bypass and mechanical (maintenance) bypass as standard.

    Backfeed protection provides additional protection at the input in the event of bypass thyristors are short circuited.
    The internal backfeed protection provides safety when fault situation occurs in static bypass line and prevents upstream energy to the input.

    Keor S 6kVA Static Uninterruptible Power Supply bears the CE marking, pursuant to Directives 73/23, 93/68, 89/336, 92/31, 93/68, and is designed and built in compliance with the following standards:
    • EN 62040-1 “General and safety requirements for UPSs used in areas that are accessible to the operator”
    • EN 62040-2 “Electromagnetic Compatibility requirements (EMC)”
    • EN 62040-3 “Performance and test method requirements”

    General Features
    UPS Topology: On line double conversion
    Architecture of the UPS: Stand alone, transformerless, On-Site Paralleling
    In/Out phase Configuration: Mono phase-Mono phase
    Neutral: Neutral Passing through
    Switching Technology: IGBT
    Backfeed Protection: Internal, standard
    Output wave form on mains operation Sinusoidal
    Output wave form on battery operation: Sinusoidal
    Standards: EN 62040-1, EN 62040-2, EN 62040-3

    Input Features
    Nominal Voltage: 230 V mono phase + neutral + PE
    Voltage Range: 195V-280V Ph-N full load
    Frequency: 45 - 65Hz
    THDi: < 7% at full load
    Power Factor: > 0.99

    Bypass
    Nominal Voltage: 230 V mono phase + neutral + PE
    Voltage Range: ±10% (adjustable)
    Frequency: ±3Hz (adjustable)
    Bypass type: Static and electro-mechanic
    Transfer time: Zero
    Manual Bypass: Built-in

    Output with Mains (AC-AC)
    Nominal Voltage: 220V, 230V, 240V mono phase + neutral + PE
    Nominal Power: 6.000 VA
    Active Power: 5.400 W
    Voltage variation (static): ± 1%
    THDv on nominal power (linear load): < 2,5%
    Frequency: 50 Hz or 60 Hz (selectable)
    Frequency tolerance: ± 0,2% Synchronized with bypass frequency
    Current Crest Factor: 2,5:1 accordingly to IEC 62040-3
    Overload capability:
    * 2min: 120% load rate with no bypass transfer
    * 30sec: 150% load rate with no bypass transfer

    Output with Mains (DC-AC)
    Nominal Voltage: 220V, 230V, 240V mono phase + neutral + PE
    Nominal Power: 6.000 VA
    Active Power: 5.400 W
    Voltage variation (static): ± 1%
    THDv on nominal power (linear load): < 2%
    Frequency: 50 Hz or 60 Hz (selectable)
    Frequency tolerance: ± 0,01% free run
    Current Crest Factor: 2,5:1 accordingly to IEC 62040-3
    Overload capability:
    * 2min: 120% load rate
    * 30sec: 150% load rate

    Battery features
    Type: Lead Acid, sealed, maintenance free VRLA
    Internal Battery Capacity *: 12 Ah (12V)
    Nominal UPS Battery Voltage: 240 Volt DC
    Max. number of possible internal battery: 20pcs
    Standard Charging Current: 1,6 A
    Additional Charger: Yes, Optional - External, mountable on battery cabinet
    Additional Charger Capacity: 2,5A
    * When used with internal transformer, batteries must be used in separate cabinet

    Environmental Specifications
    Noise level @ 1m: < 52dBA
    Operating temperature range: from 0°C to +40°C
    Stock temperature range: from -20°C to +50°C
    Humidity range: 20-95% not condensing
    Protection degree: IP31

    Manufacturing Specifications
    Net Weight without batteries **: 52 kg
    Net Weight with Int. Transformer: 100 kg
    Dimensions (WxHxD): 275 x 716 x 776 mm
    Colour: RAL 7016
    Communication Interface: 1 serial port RS232, 1 smart slot (for optional internal SNMP), 1 EPO, 1 GENSET
    Input/Output connections: 1P + N + PE
    Input/Output Circuit Breaker: 32A / 32A

    ** Total weight depends on the quantity of the installed batteries according to the required autonomy

    Doba zalohovania pri 80% zatazi: 22 minút